Three large cooling towers from a power plant emit white steam against a clear blue sky. The gray towers, adorned with red-and-white patterned tops, stand prominently in the image.

XF150MAx

For applications where extremely low drift ratings are not required, XF150MAx provides a cost-effective solution with drift loss of 0.001%. Its high surface area and nesting design provide maximum performance at minimum pressure drop.

XF150MAx Features

Specifications (XF)

English Metric
ProductBlade Spacing
inches
Depth
inches
Width
inches
Length FtBlade Thickness (after Forming)
mils
Dry Weight
lbs/ft2
Max. Height At 10° From Vertical Ft
XF80MAx
0.86
5.25
24
2 ,3, 4, 5, 6, 8, 10, 12
Standard: 13
Standard: 1.1
12
XF150MAx
1.50
5.25
12, 18
2 ,3, 4, 5, 6, 8, 10, 12
Standard: 15, Heavy Duty: 20
Standard: 1.0, Heavy Duty: 1.4
12
ProductBlade Spacing
mm
Depth
mm
Width
mm
Length
kg
Blade Thickness (after Forming)
mm
Dry Weight
kg/m2
Max. Height At 10° From Vertical
m
XF80MAx
21.8
133
610
610, 914, 1219, 1524, 1829, 2438, 3048, 3658
Standard: 0.38
Standard: 5.4
3.66
XF150MAx
38.1
133
305, 457
610, 914, 1219, 1524, 1829, 2438, 3048, 3658
Standard: 0.38, Heavy Duty: 0.51
Standard: 4.9, Heavy Duty: 6.8
3.66